Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
297
Input/holding register
Designation
Type Range Unit Default Comments
Info
Access
1)
Address high/low Bit
2-3
Signal
conditioning 2 -
type
Bit[2] 0, 1, 2,
3
0
2 = Edge rising with
memory
3 = Edge falling with
memory
r
4-5
Non-volatile
element 1 - type
Bit[2] 0, 1, 2,
3
0
r
6-7
Non-volatile
element 2 - type
Bit[2] 0, 1, 2,
3
0
r
low
0-1
EM+ - monitoring Bit[2] 0, 1, 2,
3
0
0 = on
1 = on+
2 = run
3 = run+
r
2-3
EM+ - monitoring
warning
Bit[2] 0, 1, 2,
3
0
r
4-5
Reserved
Bit[2]
0
r
6-7
Reserved
Bit[2]
0
r
Part - Bit[4]
parameters
r
0x418C high
Reset response
external fault 1
Bit[4] 0 ...
1111B
0101B Bit[0] = Panel reset
Bit[1] = Auto reset
Bit[2] = Remote reset
Bit[1] = OFF
command reset
r
Reset response
external fault 2
Bit[4] 0 ...
1111B
0101B
r
low
Reset response
external fault 3
Bit[4] 0 ...
1111B
0101B
r
Reset response
external fault 4
Bit[4] 0 ...
1111B
0101B
r
0x418D high
0-3
Hysteresis
current levels
Bit[4] 0 ... 15 1 % 5
r
4-7
EM+ - hysteresis Bit[4] 0 ... 15 1 % 5
r
low
Reserved
Bit[4]
0
r
Reserved
Bit[4]
0
r
Part - Byte
parameters
0x418E
high
Internal ground
fault - Delay
Byte 0 ...
255
100
ms
5
IM UM
(+)
r/w
low
Motor protection -
Class
Byte 5, 10 ...
35, 40
10
r/w
0x418F
high
Motor protection -
Delay with
overload
operation
Byte 0 ...
255
100
ms
5
IM UM
(+)
r/w
low
Motor protection -
Unbalance level
Byte 0 ...
100
1 % 40
IM UM
(+)
r/w