Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
198
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
3.3.2.18
Data record 160 - Communication parameters
Note
Only the address is relevant for writing. The baud rate is detected automatically. The actual
baud rate is read.
Table 3- 40 Data record 160 - Communication parameters
Byte.Bit
Designation
Type
Information
0.0
Reserved
Byte[4]
BU0 BU1 BU2(+)
4.0
Station address
Byte
5.0
Baud rate
Byte
6.0 to 9.0
Reserved
Byte[6]
10.0
PROFIsafe address (read only)
Word
BU2(+)
3.3.2.19
Data record 165 - Identification
Table 3- 41 Data record 165 - Identification
Byte.Bit
Designation
Type
Information
0.0
Reserved
Byte[4]
BU0 BU1 BU2(+)
4.0
Plant identifier
Byte[32]
36.0
Location designation
Byte[22]
58.0
Date installed
Byte[16]
74.0
Reserved
Byte[38]
112.0
Description
Byte[54]