Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
303
Input/holding register Designation
Type Range
Unit
Default Comments
Access
1)
Info
Address high/
low
Bit
2
DM-FL -
Configuration 3
Bit
0, 1
0
configuration
r
3
DM-FL -
Configuration 4
Bit
0, 1
0
r
4
DM-FL -
Configuration 5
Bit
0, 1
0
r
5
DM-FL -
Configuration 6
Bit
0, 1
0
r
6
DM-FL -
Configuration 7
Bit
0, 1
0
r
7
DM-FL -
Configuration 8
Bit
0, 1
0
r
Part - Bit[2]
parameter
r
0x4385 high 0-1 3UF50 basic type
Bit[2] 0, 1, 2
0
r
2-3
Reserved
Bit[2]
0
r
4-5 UVO timebase
Bit[2] 0, 1, 2
0
0 = 100 ms
1 = 1 s
2 = 10 s
r
6-7 UVO operating
mode
Bit[2] 0, 1, 2
0
0 = Disabled
1 = Device
connected to
voltage
(reserved)
2 = Voltage fails
r
low
0-1 Trip monitoring U<
Bit[2] 0, 1, 2
1
0 = ON (always)
1 = ON+ (always,
not TPF)
2 = RUN (motor
ON, not TPF)
r
2-3 Warning
monitoring U <
Bit[2] 0, 1, 2
1
r
4-5
Reserved
Bit[2]
0
r
6-7 Reserved
Bit[2]
0
r
0x4386 high 0-1 Trip monitoring 0/
4-20mA >
Bit[2] 0, 1, 2, 3
0
r
2-3 Warning monitoring
0/4-20mA >
Bit[2] 0, 1, 2, 3
0
r
4-5 Trip monitoring 0/
4-20mA <
Bit[2] 0, 1, 2, 3
0
r
6-7 Warning monitoring
0/4-20mA <
Bit[2] 0, 1, 2, 3
0
r
low
0-1 Monitoring limit 1
Bit[2] 0, 1, 2, 3
0
r
2-3 Monitoring limit 2
Bit[2] 0, 1, 2, 3
0
r
4-5 Monitoring limit 3
Bit[2] 0, 1, 2, 3
0
r
6-7 Monitoring limit 4
Bit[2] 0, 1, 2, 3
0
r