Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
180
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Byte.Bit Designation (PRM group)
Type Range
Unit
Default Note
Information
50.0
Truth table 3 type 3I/1O
Byte 0 -
1111111
1B
0
BU0 BU1 BU2(+)
51.0
Reserved
Byte
0
52.0
Word parameters (32)
52.0
Motor protection - Cooling
down period
Word 600 -
65535
100 ms 3000
IM / UM(+)
54.0
Motor protection - Pause
time
Word 0 -
65535
100 ms 0
0 = disabled
IM / UM(+)
56.0
Execution time
Word 0 -
65535
100 ms 10
0 = disabled
BU0 BU1 BU2(+)
58.0
Monitoring the number of
starts - Time range for
starts
Word 0 -
65535
1 s
0
BU0 BU1 BU2(+)
60.0
Monitoring the number of
starts - Interlocking time
Word 0 -
65535
1 s
0
BU0 BU1 BU2(+)
62.0
Motor stop time level >
Word 0 -
65535
1 h
0
BU0 BU1 BU2(+)
64.0
Timer 1 - Limit
Word 0 -
65535
100 ms 0
BU0 BU1 BU2(+)
66.0
Timer 2 - Limit
Word 0 -
65535
100 ms 0
BU0 BU1 BU2(+)
68.0
Counter 1 - Limit
Word 0 -
65535
0
BU0 BU1 BU2(+)
70.0
Counter 2 - Limit
Word 0 -
65535
0
BU0 BU1 BU2(+)
72.0
EM+
2)
- trip level
Word 30 -
40000
1 mA
1000
BU0 BU2(+)
74.0
EM+
2)
- warning level
Word 30 -
40000
1 mA
500
BU0 BU2(+)
76.0
D-word parameters (36)
76.0
Operator control enable
Bit
[32]
0 ...
1..1B
0..0B
80.0
Motor protection - set
current I
s
1
D-
word
1)
10 mA 30
IM / UM(+)
84.0
Motor operating hours
level >
D-
word
0 -
0xFFFF
FFFF
1 s
0
BU0 BU1 BU2(+)
88.0
Reserved
D-
word
0
1) Value range dependent on current range of the IM / UM and the conversion factor;
bit 31 = 1, i.e. conversion factor is active
2) 3UF7510-1AA00-0 ground-fault module
3) Class 7 only for BU2+