Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
94
Manual, 05/2011, A5E03648639-01
Single Counting - Main Count Direction Up
In single counting mode with main count direction up, when the gate is opened, the
FM 350-1 counts up or down from the load value until the high count limit is exceeded.
If the high count limit is exceeded, the following occurs:
●
The gate is closed
●
The STS_OFLW bit in the feedback interface is set
●
The counter is loaded with the load value
The high count limit can be set. The load value has a starting count and can be changed.
You must open the gate again to restart the counting.
676B2)/:
6HWXSSHU
FRXQWOLPLW
/RDGYDOXH
/RZHUFRXQW
OLPLW
6HWFRXQW
UDQJH
&RXQWHUOHYHO
*DWHVWDUW
*DWHVWDUW
$XWRPDWLF
JDWHVWRS
$XWRPDWLF
JDWHVWRS
7LPH
Figure 7-3
Single counting without main count direction; canceling gate function