Installing and removing FM 350-1
2.1 Preparing for installation
FM 350-1 Counter module
20
Manual, 05/2011, A5E03648639-01
2.1
Preparing for installation
Important Safety Information
There are important rules you must observe for integrating an S7-300 with an FM 350-1 into
a plant or a system. These rules and directives are explained further in the /1/ manual.
Vertical or Horizontal Arrangement
Give preference to horizontal installation of the rack. In case of vertical installation of the rack
limited ambient temperatures (max. 40 °C) apply for the modules.
Specifying the Slot
The 350-1 function module can be installed like a signal module in any of Slots 4 to 11.
Rules for Configuring the Mechanical Installation
Refer to manual /1/ for possibilities for the mechanical structure and how to proceed when
configuring. The following offers brief extra information.
●
A maximum of eight SMs or FMs are permissible per rack.
●
The maximum number is restricted by the width of the modules or the length of the
mounting rail. The FM 350-1 requires an installation width of 40 mm.
●
The maximum number is restricted by the total current consumptions of all modules to the
right of the CPU and that are supplied from the 5 V backplane bus supply. The current
consumption of the FM 350-1 amounts to 160 mA.
●
The maximum number is restricted by the memory required by the CPU software for
communications with the FM 350-1.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...