Technical data
11.2 Technical data
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
185
Digital outputs
Supply voltage
2L+ / 2M
Electrical isolation
Yes, against all other circuits, except digital inputs
Output voltage
High signal "1"
Low signal "0"
min. 2L+ - 1.5 V
max. 3 V
Switching current
Rated value
Range
0.5 A
5 mA to 0.6 A
Rise time
max. 300 µs
Shut-off voltage (inductive)
limited to 2L+ - (45 V to 55 V)
short circuit-proof
Yes
5-V count inputs
Level
to RS422
Terminating resistor
approx. 220 Ohms
Differential input voltage
min. 1.3 V
Maximum count frequency
500 kHz
Electrical isolation to S7-300 bus
No
Input frequency and cable length of symmetrical 5-V
incremental encoder
max. 500 kHz at 32 m length of the cable, shielded
Input frequency and cable length of symmetrical 24-V
incremental encoder
max. 500 kHz at 100 m length of the cable, shielded
24-V count inputs
Low level
-30 V to +5 V
High level
+11 V to +30 V
Input current
typically 9 mA
Minimum pulse width (max. count frequency)
≥ 2.5 µs (200 kHz), ≥ 25 µs (20 kHz) (assignable)
Electrical isolation to S7-300 bus
No
Input frequency and cable length of asymmetrical encoders
(count or digital inputs)
Max. 200 kHz at 20 m length of the cable, shielded
Input frequency and cable length of asymmetrical encoders
(count or digital inputs)
Max. 20 kHz at 100 m length of the cable, shielded
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...