Programming the FM 350-1
5.2 The function FC CNT_CTL1 (FC 2)
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
45
Time Required to Transfer Values
Table 5- 6
Time Required to Transfer Values
Use of the FM 350-1
Time requirement
Centralized
At least 4 OB 1 cycles
Distributed
(Non-isochronous mode)
At least 5 PROFIBUS DP cycles
At transmission of
only one value
5 PROFIBUS DP cycles
Distributed
(Isochronous mode)
At simultaneous
initiation of the
transmission of
several values
for the 1st value: 5 PROFIBUS DP cycles after initiation
for the 2nd value: 6 PROFIBUS DP cycles after initiation
for the 3rd value: 7 PROFIBUS DP cycles after initiation
Parameters for Transferring Values in the DB (Count Modes)
The following table shows the range of the DB in which you transfer the LOAD_VAL,
CMP_V1 and CMP_V2 parameters.
The LOAD_VAL parameter (bytes 14 to 17) has two meanings:
●
If you set function parameter L_DIRECT or L_PREPAR, LOAD_VAL is interpreted as a
load value.
●
If you set function parameter C_DOPARA, you can use Byte 14 to define the behavior of
outputs DO0 and DO1. Bytes 15 and 16 are interpreted as hysteresis and pulse duration.
Table 5- 7
Parameters for Transferring Values in the DB (Count Modes)
DB address
Parameters
Meaning
14.0
LOAD_VAL
Load value; direct and preparatory loading with function parameter L_DIRECT
Load value; preparatory loading with function parameter L_PREPAR
The behavior of outputs DO0 and DO1, hysteresis and pulse duration, are defined using
function parameter: C_DOPARA
Bit 3
Bit 2
Bit 1
Bit 0
Reaction of output DO0
x
0
0
0
Inactive
x
0
0
1
Active from comparison value to overflow
x
0
1
0
Active from comparison value to underflow
x
0
1
1
Active on reaching the comparison value for pulse
duration (up/down)
x
1
0
0
Active on reaching the comparison value for pulse
duration (up)
14.0
LOAD_VAL
x
1
0
1
Active on reaching the comparison value for pulse
duration (down)
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...