Operating Modes, parameters and commands
7.4 Measuring modes
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
139
Isochronous mode
When operating in isochronous mode, FM 350-1 accepts the control signals output by the
control interface at time T
o
in each PROFIBUS DP cycle. As a result, all control operations
are executed in isochronous mode and take effect at the time T
o
. The reaction to the control
signals is reported within the same PROFIBUS DP cycle.
FM 350-1 returns a measured value and the status bits at time T
i
in each PROFIBUS DP
cycle
.
Each measurement starts and ends at the time T
i
.
Note
As you need to define the update time as an integer multiple of 10 ms for operation in non-
isochronous mode, and in integer multiples of the PROFIBUS DP cycle time for operation in
isochronous mode, you should also adapt the update time parameter when you toggle these
modes in order to retain the actual update time.
Commands in the measuring modes
You can control measurements at FM 350-1 by executing the following commands.
Table 7- 31 Commands of FM 350-1
Designation
Description
Open and close gate
You start the measurement by opening a gate, and stop it by closing
this gate.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...