![Siemens SIMATIC S7-300 FM 350-1 Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/siemens/simatic-s7-300-fm-350-1/simatic-s7-300-fm-350-1_manual_1265384043.webp)
Programming the FM 350-1
5.2 The function FC CNT_CTL1 (FC 2)
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
43
CNT_CTL1 Function Parameters
Table 5- 3
The Parameters of the CNT_CTL1 Function
Name
Declaration type Data type
Meaning
The user...
The block...
DB_NO
INPUT
INT
DB number with the counter data
enters
polls
SW_GATE
INPUT
BOOL
Counter control bit "SW gate
(start/stop)"
sets and resets polls
GATE_STP
INPUT
BOOL
Counter control bit "Gate stop"
sets and resets polls
OT_ERR_A
INPUT
BOOL
Acknowledge operator error
sets and resets polls
SET_DO0
INPUT
BOOL
Set/Reset DO0
sets and resets polls
SET_DO1
INPUT
BOOL
Set/Reset DO1
sets and resets polls
OT_ERR
OUTPUT
BOOL
Operator error occurred
polls
sets and resets
Counting: Trigger bit for "direct
and preparatory loading" of a
counter
sets
L_DIRECT
2)
IN-OUT
BOOL
Measuring: Must NOT be set
-
polls and resets
Counting: Trigger bit for
"preparatory loading" of a counter
L_PREPAR
2)
IN-OUT
BOOL
Measuring: Transfer of the low
limit
sets
polls and resets
Counting: Transfer "Comparison
value 1" trigger bit
T_CMP_V1
2)
IN-OUT
BOOL
Measuring: Transfer of the high
limit
sets
polls and resets
Counting: Transfer "Comparison
value 2" trigger bit
T_CMP_V2
2)
IN-OUT
BOOL
Measuring: Update time
sets
polls and resets
C_DOPARA
1)
IN-OUT
BOOL
Trigger bit for parameter change
sets
polls and resets
RES_SYNC
IN-OUT
BOOL
Reset "Synchronization" status bit sets
polls and resets
RES_ZERO
IN-OUT
BOOL
Reset zero crossing, overflow,
underflow and comparator or end
of measurement status bit
sets
polls and resets
1)
This parameter must not be set at the same time as one of the parameters L_DIRECT, L_PREPAR, T_CMP_V1 or
T_CMP_V2.
2)
This parameter must not be set at the same time as the C_DOPARA parameter.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...