Product Overview
1.1 Properties
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
11
Diagnostic Interrupt
The FM 350-1 can trigger a diagnostics interrupt if any of the following occur:
●
External auxiliary voltage faulty
●
Fault in 5.2 VDC encoder supply
●
Module not assigned parameters or errors in parameter assignment
●
Watchdog timeout
●
RAM defective
●
Hardware interrupt lost
●
Fault in signal A, B or N of the 5 V encoder
Pulse Duration
You can specify a pulse duration for the digital outputs of the FM 350-1. The pulse duration
is used to specify how long the corresponding digital output is to be set. A value between 0
and 500 ms may be set for the pulse duration. This value applies to both outputs. You can
adapt the FM 350-1 to existing actuators by specifying a pulse duration.
Which Signals Can the FM 350-1 Register?
The FM 350-1 can register the signals from the following sources:
●
Incremental 5-V encoders
●
Incremental 24-V encoders
●
24-V pulse encoders with direction level
●
24-V initiators without direction level for example, light barrier or BERO
●
Internal 1 MHz time base
Input Filters
For the purpose of suppressing interference, you can assign input filters (RC elements) with
a uniform filter time for the 24 V inputs A*, B*, and N* and for the digital inputs. The following
two input filters are available:
Table 1- 1
Input filter
Characteristics
Input Filter 1
(default)
Input Filter 2
Typical input delay
1 μs
15 μs
Maximum count frequency
200 kHz
20 kHz
Minimum pulse width of the count signals
2.5 μs
25 μs
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...