Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
122
Manual, 05/2011, A5E03648639-01
Setting the Counter with DI Set
The counter can be loaded with the load value by means of a rising pulse edge across
DI Set.
You can set the response of the FM 350-1 to a positive pulse edge across DI Set by means
of the tags ENSET_UP and ENSET_DN in the DB of the FC CNT_CTL1 and by
parameterization.
Table 7- 26 Setting the Counter with DI Set
Parameters
Behavior of the FM 350-1
ENSET_UP set
The counter is only set in the case of up counting
ENSET_DN set
The counter is only set in the case of down counting
ENSET_UP and
ENSET_DN set
The counter is set in the case of up and down counting
Parameter assignment
"single setting of
counter"
The counter is set only at the first rising edge at DI Set.
If the counter is to be set again, you must first set ENSET_UP or
ENSET_DN again. The counter is then set again with the next positive edge
at DI Set.
Parameter assignment
"Multiple setting of
counter"
As long as ENSET_UP and/or ENSET_DN are set, the counter will be set
with each rising edge at DI-Set.
Note
It is imperative that you set one of the two tags ENSET_UP or/and ENSET_DN so that the
counter can be set via digital input DI Set.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...