Wiring the FM 350-1
3.2 Wiring front connectors
FM 350-1 Counter module
32
Manual, 05/2011, A5E03648639-01
Terminal 2 (1M) of the front connector must have a low-resistance connection to the ground
of the CPU. If you supply the encoder with an external voltage, you must also connect the
ground of this external voltage with the CPU ground.
$
%
1
'&9
0
6KLHOGRQ
VKLHOGVXSSRUW
)URQWFRQQHFWRU
6KLHOGRQ
KRXVLQJ
Figure 3-3
Details Regarding the Connection of an Incremental 24V Encoder
●
Use flexible cables with cross-sections of 0.25 to 1.5 mm
2
.
Note
If the encoders are supplied via the module, the cable cross-section must be large
enough to carry the required voltage to the encoder despite voltage drops over the cable.
This applies especially in the case of incremental 5 V encoders.
●
You do not need wire end ferrules. If you use wire end ferrules then use only those
without insulation collar in accordance with DIN 46228 Form A, short version!
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...