![Siemens SIMATIC S7-300 FM 350-1 Скачать руководство пользователя страница 128](http://html.mh-extra.com/html/siemens/simatic-s7-300-fm-350-1/simatic-s7-300-fm-350-1_manual_1265384128.webp)
Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
128
Manual, 05/2011, A5E03648639-01
Function principle
The counter function is enabled by opening the SW gate.
The counter and latch values are assigned a start value. These values do not change by
opening the SW gate.
The first edge at input DI-Start starts the count at the load value.
The counter will be initialized with the load value at each further edge at input DI-Start.
The latch value is always equivalent to the counter value at the time the edge trigger is
generated.
The status at input DI-Start is indicated at the STS_STA status bit in the DB.
The latch value is indicated at LATCH_LOAD in the DB.
*$7(B673
6:B*$7(
',6WDUW
&RXQWSXOVHV
&RXQWHUOHYHO
/DWFKYDOXH
Figure 7-27 Latch/Retrigger when load value = 0 and positive edge at DI-Start