Programming the FM 350-1
5.7 Programming FM 350-1 without FCs
FM 350-1 Counter module
64
Manual, 05/2011, A5E03648639-01
Description of the control bits for measuring modes
Table 5- 17 Description of the control bits for measuring modes
Control bits
Explanation
C_DOPARA
Set this bit to change the reaction and function of DO0.
The values at byte 0 are accepted as new function of DO0.
Transfer the old values if you want to discard all changes.
CTRL_DO0
Enable DO0
Set this bit to enable output DO0.
CTRL_DO1
Enable DO1
Set this bit to enable output DO1.
GATE_STP
Set this bit to close the internal gate.
L_PREPAR
Set this bit to load the low limit.
NEUSTQ
Set this bit to acknowledge a startup of FM 350-1.
After its restart, FM 350-1 will not recognize any control or data input unless this bit has been
set. FC CNT_CNTL1 sets the NEUSTQ bit when the return signal FM_NEUST is set, and the
return signal FM_NEUSTQ = 0. FC CNT_CNTL1 resets the bit when FM 350-1 has reset the
FM_NEUST bit and set the FM_NEUSTQ bit.
If you are not using FC CNT_CNTL1, the restart must be coordinated in the user program.
OT_ERR_A
Set this bit to acknowledge an operator error.
For detailed information on operator errors, read the checkback interface before you
acknowledge the error. The error message is no longer valid after its acknowledgement.
RES_ZERO
Set this bit to reset the acknowledgement bits STS_OFLW, STS_UFLW and STS_COMP1.
SET_DO0
Provided you have set the output reaction "inactive", and the enable bit CRTL_DO0 is set, you
can use this bit to toggle the digital output DO0 on and off.
SET_DO1
Provided you have set the output reaction "inactive", and the enable bit CRTL_DO1 is set, you
can use this bit to toggle the digital output DO1 on and off.
SW_GATE
Set/reset this bit to open/close the SW gate.
T_CMP_V1
Set this bit to load the high limit.
T_CMP_V2
Set this bit to load the refresh interval time.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...