Wiring the FM 350-1
3.2 Wiring front connectors
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
31
3.2
Wiring front connectors
Cables
Here are some rules for you to observe when selecting cables:
●
The cables for digital inputs DI Start, DI Stop and DI Set must be shielded.
●
The cable for the counter signals must be shielded.
●
You must apply the shields of the counter signal cables both at the pulse encoder and in
the immediate vicinity of the module via the shield attachment, for example.
●
The following cables of the incremental 5 V encoder have to be twisted in pairs.
–
A and /A
–
B and /B
–
N and /N
$
$
%
%
1
1
'&9
0
6KLHOGRQ
VKLHOGVXSSRUW
6KLHOGRQ
KRXVLQJ
)URQWFRQQHFWRU
7ZLVWHGFDEOHV
Figure 3-2
Details Regarding the Connection of an Incremental 5V Encoder