![Siemens SIMATIC S7-300 FM 350-1 Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/siemens/simatic-s7-300-fm-350-1/simatic-s7-300-fm-350-1_manual_1265384022.webp)
Installing and removing FM 350-1
2.2 Installation of the FM 350-1
FM 350-1 Counter module
22
Manual, 05/2011, A5E03648639-01
Procedure for the Installation
How to mount the FM 350-1 on the mounting rail:
1.
Switch the CPU to STOP. Switch off the power supply.
2.
An bus connector is enclosed with the FM 350-1. Plug this into the bus connector of the
module to the left of the FM 350-1. (The bus connector is located on the back and you
may have to loosen the neighboring module.)
3.
Hang the FM 350-1 onto the rail and swing it down.
4.
Tighten the screw on the FM 350-1 (tightening torque approximately 0.8 to 1.1 Nm).
If you want to install further modules to the right of the FM 350-1, first connect the
expansion bus of the next module to the right-hand backplane bus connector of the
FM 350-1.
If the FM 350-1 is the last module in the rack, do not connect an expansion bus!
5.
Label the FM 350-1 with its slot number. Use the number wheel supplied with the CPU for
this purpose.
Manual /1/ describes the numbering scheme you must use and how to connect the slot
numbers.
6.
Install the shield connecting element
Further Notes
Manual /1/ contains further notes on installing and removing modules.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...