Operating Modes, parameters and commands
7.4 Measuring modes
FM 350-1 Counter module
138
Manual, 05/2011, A5E03648639-01
Limit monitoring
On expiration of the update time, the module compares the measured value (frequency,
speed or period) with the set low and high limits.
If the module detects an underflow of the actual measured value (measured value < low
limit), it sets the status bit STS_UFLW = 1. A hardware interrupt may also be generated.
If the module detects an overflow of the actual measured value (measured value > high
limit), it sets the status bit STS_OFLW = 1. A hardware interrupt may also be generated.
676B2)/:
676B8)/:
/RZHUOLPLW
8SSHUOLPLW
0HDVXUHG
YDOXH
Figure 7-31 Limit monitoring in measuring mode
Reset the STS_OFLW and STS_UFLW bits by setting the RES_ZERO and STS_RES_ZERO
bits according to the acknowledgement principle. The module sets the status bits again if it
detects overflow of the measured value after the acknowledgement bits were set.
If programmed accordingly, you also can use the limit monitoring function to set output DO0.
Gate control
You can control, i.e. start and stop, measurements at FM 350-1 using the HW and SW
gates.
Start values after programming
Table 7- 30 Start value
Value
Start value
Low limit
programmed value
High limit
programmed value
Refresh time
programmed value
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...