![Siemens SIMATIC S7-300 FM 350-1 Скачать руководство пользователя страница 112](http://html.mh-extra.com/html/siemens/simatic-s7-300-fm-350-1/simatic-s7-300-fm-350-1_manual_1265384112.webp)
Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
112
Manual, 05/2011, A5E03648639-01
Status of the Outputs and Status Bits
The status of the two outputs is indicated by the green LEDs and the corresponding status
bits in the DB.
Table 7- 20 Output DO0
Comparison
condition
Enable bit
CTRL_DO0
Status bit
STS_COMP1
Status bit
STS_CMP1/
Output DO0
LED DO0
0
0
0
Out
Not fulfilled
1
0
0
Out
0
1
0
Out
Fulfilled
1
1
1
Is lit
Table 7- 21 Output DO1
Comparison
condition
Enable bit
CTRL_DO1
Status bit
STS_COMP2
Status bit
STS_CMP2/
Output DO1
LED DO1
0
0
0
Out
Not fulfilled
1
0
0
Out
0
1
0
Out
Fulfilled
1
1
1
Is lit
Status bits STS_CMP1 and STS_CMP2 indicate the current status of outputs DO0 and DO1.
If enabled, they are set by CTRL_DO0 and CTRL_DO1 if a comparison condition is fulfilled
and are reset if the condition is not fulfilled.
Status bits STS_COMP1 and STS_COMP2 are set by CTRL_DO0 and CTRL_DO1 if a
comparison condition is fulfilled, regardless of whether they are enabled, and remain set until
you acknowledge the status bits with RES_ZERO.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...