Commissioning FM 350-1
6.2 Procedure for assigning parameters
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
79
Working step
Options/Procedure
✓
Gateless (continuous counting only)
SW gate
HW gate
Latch
Gate control
Latch/retrigger
Cancel
Gate function
Interrupt
Positive edge
Negative edge
Latch
Both edges.
Determine the behavior of the digital inputs
Level-controlled hardware gate
HW gate
Edge-controlled hardware gate
≥2.5 μs
Minimum pulse width
≥25 μs
Single
Setting the counter
Multiple
Evaluate zero mark for setting
Determine the behavior of the digital outputs
Pulse duration
0 to 500 ms
Hysteresis
0 to 255
Inactive
Active from Comparison value 1 to overflow
Active from Comparison value 1 to underflow
Active on reaching Comparison value 1 for pulse
duration (up/down)
Active on reaching Comparison value 1 for pulse
duration (up)
Active on reaching Comparison value 1 for pulse
duration (down)
0
Configuring FM 350-1 in
HW Config
Output DO0
Substitute value for CPU
stop
1
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...