Errors and diagnostics
10.3 Data error
FM 350-1 Counter module
180
Manual, 05/2011, A5E03648639-01
10.3
Data error
Data error events
FM 350-1 checks all new parameters it receives. The module reports any errors returned in
this check.
Where data errors are indicated
FC CNT_CTL1 enters the data errors and the error number in the DB of FC CNT_CTL1. You
can access this data word in the user program using the variable identifier `DA_ERR_W'.
Possible data errors
Table 10- 4 Data error numbers and their meaning
No.
Meaning
0
No error
200
Coding plug in wrong position or missing
201
The position of the coding plug does not match the programmed encoder
202
Invalid diagnostics value of the signal pair
203
Incorrect value for signal evaluation
204
Invalid value at the input filter for 24-V count signals
205
Invalid value at digital input filters
206
Reversal of direction not allowed
207
Incorrect configuration of the reaction of DO0
208
Incorrect configuration of the reaction of DO1
209
Pulse duration out of limits
211
Wrong operating mode selected
212
No gate or both gates defined
213
Faulty parameters of main count direction
214
Count high limit exceeded
215
A count direction other than set at the hardware interrupt parameter `Reaching the
comparison value in up or down count direction' was defined in the configuration of the
Outputs `Active on reaching the comparison value of the pulse duration for up or down
counts'. The directions set must match.
216
Gate control interrupts are only possible in modes with gate control.
217
Interrupt on reaching comparison values is not allowed when the output reaction "Active
within the range between the comparison value and overflow" or "Active within the range
between the comparison value and underflow".
218
Interrupt triggering at the zero transition is not allowed
219
Wrong coding of the "Latch Setting"
220
Faulty gate control parameters
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...