Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
129
Interrupting and canceling the command
When you close the software gate, counting is interrupted (interrupting gate function); this
means counting resumes at the most recent count value the next time the software gate
opens.
The current count is also stored at an edge at digital input DI-Start with a closed software
gate and the count begins again with the load value.
However, counting is terminated if you close the SW gate by executing GATE_STP of
FC CNT_CTL1. The signal at input DI-Start can thus no longer be used to save any counter
values.
Hardware interrupt on latch/retrigger commands
A hardware interrupt may be triggered each time a counter values is saved by executing the
latch/retrigger command. As a consequence, you may need to increase the interval between
the edges. The hardware interrupts will be lost if the interrupt rate is higher than the
acknowledgement rate of the system. This situation is reported by a diagnostic interrupt.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...