Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
132
Manual, 05/2011, A5E03648639-01
Canceling and terminating the command
When you close the software gate, counting is cancelled (canceling gate function); this
means counting begins again at the load value the next time the software gate opens.
The current count is also stored at an edge at digital input DI-Start with a closed software
gate and the count does not change.
However, counting is terminated if you close the SW gate by executing GATE_STP of
FC CNT_CTL1. DI-Start can then no longer be used to save any counter values.
Hardware interrupt on latching
A hardware interrupt may be triggered each time a counter value is saved by latching. As a
consequence, you may need to increase the interval between the edges. The hardware
interrupts will be lost if the interrupt rate is higher than the acknowledgement rate of the
system. This situation is reported by a diagnostic interrupt.
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...