Encoder signals and their evaluation
8.3 24-V signals
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
165
Input filters for the 24-V count inputs
For the purpose of suppressing interference, you can parameterize input filters with a
uniform filter time for the 24 V inputs A*, B* and N* and for the digital inputs. Input filters
available:
Table 8- 3
Input filters
Features
Input filter 1
(default)
Input filter 2
Typical input delay
1 µs
15 µs
Maximum count frequency
200 kHz
20 kHz
Minimum pulse width of count signals
2.5 µs
25 µs
Monitoring encoder signals
The 24-V count signals are not monitored to detect wire-breaks or short-circuits.
Coding plug (only for FM 350-1)
To operate this encoder, insert the coding plug in position D.