Commissioning FM 350-1
6.2 Procedure for assigning parameters
FM 350-1 Counter module
78
Manual, 05/2011, A5E03648639-01
6.2
Procedure for assigning parameters
Check lists
Use the check lists below to check and document the working steps for parameterizing the
FM 350-1.
Table 6- 2
Check list for Count Modes
Working step
Options/Procedure
✓
Select encoder
A + B + N
A + B
A
5-V encoder with
symmetrical signals
Monitoring
None
≤200 kHz/≥2.5 μs
Max. count frequency
≤20 kHz/≥25 μs
Sinking output
24-V encoder with
asymmetrical signals
Encoder inputs
Sourcing output/push-pull
≤200 kHz/≥2.5 μs
Max. count frequency
≤20 kHz/≥25 μs
Sinking output
24 V encoders with pulse
train and direction signal
Encoder inputs
Sourcing output/push-pull
≤200 kHz/≥2.5 μs
Max. count frequency
≤20 kHz/≥25 μs
Sinking output
24 V initiator
Encoder inputs
Sourcing output/push-pull
Internal 1 MHz time base
Single
Double
Signal evaluation
Quadruple
Normal
Count direction
Inverted
Set operating mode
Continuous counting
Single counting
Periodic counting
0 to +32 bit
Set count range
-31 to +31 bit
None
Up
Configuring FM 350-1 in
HW Config
Main count direction
(only with single counting or
periodic counting)
Down
Содержание SIMATIC S7-300 FM 350-1
Страница 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Страница 168: ...Encoder signals and their evaluation 8 4 Signal evaluation FM 350 1 Counter module 168 Manual 05 2011 A5E03648639 01 ...
Страница 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Страница 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Страница 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Страница 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...