3.32
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Differential, Restricted Earth Fault, Thermal, and Overcurrent Elements
Thermal Element (SEL-387-6 Relay)
Protocol Setting (PROTO)
Range: SEL, LMD, RTDA, RTDB, DNP
Select the RTDA or RTDB protocol under the Port settings (SET P
n
,
n
= 1–
4), to enable communication with the SEL-2600A.
Number of RTDs in Use (RTDNUMA, RTDNUMB)
Range: 0. . .12
Enter the number of RTDs to be used for Group A. Group B has a similar
setting.
Type of RTDs (RTD1TA—RTD12TA)
Range: NA, PT100, NI100, NI120, CU10
Enter the type of metal: platinum, nickel, or copper. Based on the RTD
n
TA
setting (where
n
is the RTD number), the data for the specified RTD type will
be used to update the associated RTD temperature value.
Type of RTDs (RTD1TB—RTD12TB)
Range: NA, PT100, NI100, NI120, CU10
Enter the type of metal: platinum, nickel, or copper. Based on the RTD
n
TB
setting (where
n
is the RTD number), the data for the specified RTD type will
be used to update the associated RTD temperature value.
Thermal Element (SEL-387-6 Relay)
Application
Description
The SEL-387-6 provides a thermal element based on IEEE Standard
C57.91-1995,
IEEE Guide for Loading Mineral-Oil-Immersed Power
Transformers
. Use this element to activate a control action or issue a warning
or alarm when your transformer overheats or is in danger of excessive
insulation aging or loss of life. Capture current hourly or daily data about your
transformer using the thermal event report. The data acquisition interval is one
minute, which constitutes the maximum element timing error. This very short
time interval makes the element suitable for both thermal protection and
control functions.
Operating
Characteristic
The SEL-387 thermal element compares top-oil,
TO
, and winding hot-spot,
H
, temperatures against thresholds beyond which a Relay Word bit will
assert. You can use these bits to alarm for overheating of the transformer
(
). Top-oil temperature is a calculation of the transformer oil
temperature, while hot-spot temperature is a calculation of the hottest point on
the transformer winding. The thermal element uses top-oil temperature and
hot-spot temperature to calculate the insulation aging acceleration factor,
FAA, daily rate of loss of life, RLOL, and total loss of life, TLOL. For each of
these quantities you can set a threshold beyond which a Relay Word bit will
assert (
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...