10.19
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Testing and Troubleshooting
Acceptance Testing
Step 2. Purpose: Set the Sequential Events Recorder to record the
element timing.
Method:
a. Use
SET R SER1 <Enter>
to set SER1 equal to the
element pickup and time-out Relay Word bits (i.e.,
50G4, 32IF, and REFP).
b. When prompted, set SER2, SER3, and SER4 to NA.
c. Save the settings.
Step 3. Purpose: Connect and apply two single current test sources to
test the REF element.
Method:
a. Connect two single current test sources as shown in
, but with source current 2 connected to one
of the Winding 4 inputs (e.g.,
IAW4
).
b. Set the
IAW1
current magnitude to:
IAW1
2 • 50GP • CTR4/CTR1
c. Using the default CT ratios,
IAW1
should be set to at least
2 • 0.5 A • 400/120, or 3.33 A.
d. Set the magnitude of
IAW1
to 4 A; set the angle of
IAW1
to
180 degrees.
e. Set the
IAW4
current at 1 A at zero degrees. Since the
currents are opposite in phase, nothing should happen.
Verify this as follows:
f.
Execute the
TAR 21
command. Relay Word bits 50G4,
32IR, 32IF, and REFP are all in this row. With the
currents applied as above, 50G4 should be 1, and REFP
should remain at 0. Bit 32IR should be 1, indicating an
external (reverse) fault. Bit 32IF should be 0.
g. Change the angle of
IAW1
to zero degrees, or any value
within about ±80 degrees of
IAW4
. The REF element
should function.
Verify this as follows:
h. Execute the
TAR 21
command again. 50G4 should still
be 1, REFP should be 1 (indicating time-out), 32IR
should be 0, and 32IF should be 1 (indicating an
internal, or forward, fault).
Step 4. Purpose: Verify the operation time.
Method:
a. Type
SER <Enter>
to view the SER records. The
assertion and deassertion of each element listed in the
SER1, 2, 3, and 4 settings are recorded.
b. Subtract the time of assertion of the directional element
(32IF) from the assertion time of the time-out bit
(REFP). This is the operate time, which should be about
one second, as calculated above. (50G4 will have
remained asserted from earlier in the test, since no
change was made to the
IAW4
current.)
SER C
clears
the SER records.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...