9.20
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Event Reports and SER
Sequential Events Recorder (SER) Event Report
To rename a Relay Word bit with an ALIAS
n
setting, use
SET R
to access the
settings. For each “ALIAS
n
=” setting, list the bit name; a separator, which
can be one of the following characters: = ; : ' , / \ ? "; and then the desired
name, which can include as many as 15 characters. For example, one setting
might be ALIAS2 = CLS1 BKR1CLOSE. Instead of CLS1 being listed in the
report, the name BKR1CLOSE will appear, indicating that a Breaker 1 close
operation was performed.
In addition to the SER
n
trigger settings, if the relay is newly powered up or a
settings change is made, a row is triggered in the SER event report with the
message:
Relay newly powered up or settings changed.
Each entry in the SER includes SER row number, date, time, element name,
and element state. Generally, the rows are listed from top to bottom in
chronological order, oldest first, to facilitate analyzing the sequence. The
newest records have the lowest row numbers, the oldest records the highest
row numbers.
Making SER Event
Report Trigger
Settings
Each SER trigger setting (SER1, SER2, SER3, or SER4) can be set with up to
24 elements (Relay Word bits from
). Thus, up to 96
total elements can be monitored for SER event report row triggering.
The SER settings can be made using spaces or commas as delimiters between
elements. For example, if setting SER1 is made as follows:
SER1 =
IN101,IN102 IN103,,IN104 , IN105, , IN106
The relay displays the settings as:
SER1 = IN101,IN102,IN103,IN104,IN105,IN106
Retrieving SER Event
Report Rows
The latest 512 rows of the SER event report are stored in nonvolatile memory.
Row 1 is the most recently triggered row, and row 512 is the oldest. These
lines are accessed with the
SER
command in the following ways shown in
:
NOTE:
Alias names can consist of all
printable characters (including
spaces).
Table 9.9
Different SER Event Report Responses
(Sheet 1 of 2)
Example SER Serial
Port Commands
Format
SER
If
SER
is entered with no numbers following it,
all available rows are displayed (up to row number 512).
They display with the oldest row at the beginning (top)
of the report and the latest row (row 1) at the end (bottom)
of the report. Chronological progression through the report
is down the page and in descending row number.
SER 17
If
SER
is entered with a single number following it
(17 in this example), the first 17 rows are displayed, if they exist.
They display with the oldest row (row 17) at the
beginning (top) of the report and the latest row (row 1) at the end
(bottom) of the report. Chronological progression through the
report is down the page and in descending row number.
SER 10 33
If
SER
is entered with two numbers following it (10 and 33
in this example; 10 < 33), all the rows between (and including)
rows 10 and 33 are displayed, if they exist. They display with
the oldest row (row 33) at the beginning (top) of the report and
the latest row (row 10) at the end (bottom) of the report.
Chronological progression through the report is down the page
and in descending row number.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...