9.7
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Event Reports and SER
Standard 15-, 30-, or 60-Cycle Event Reports
Event D (Digital Event Report)
The digital event report contains the status of the instantaneous, definite-time,
and inverse-time overcurrent phase, single-phase, calculated residual, and
negative-sequence overcurrent elements and the demand current thresholds for
phase, calculated residual, and negative-sequence for each of the four winding
inputs. The status of the Relay Word bits TRIP
n
(
n
= 1, 2, 3, 4, and 5) as well
as the status of the eight digital outputs and six optoisolated inputs are also
included.
Use the
EVENT D
command to retrieve digital event reports. There are
several options to customize the report format. The general command format
is:
EVE D
[
n
,
S
x
,
L
y
[
–
[
w
]]] (parameters in [ ] are optional)
for an example digital event report. This example event
report displays rows of information each quarter-cycle and was retrieved with
the
EVE D <Enter>
command.
Table 9.3
Winding Event Report Output and Input Columns
Column Heading
Symbol
Definition
All
.
All indication deasserted
OUT 12
1
2
b
Output contact
OUT101
asserted
Output contact
OUT102
asserted
Both
OUT101
and
OUT102
asserted
OUT 34
3
4
b
Output contact
OUT103
asserted
Output contact
OUT104
asserted
Both
OUT103
and
OUT104
asserted
OUT 56
5
6
b
Output contact
OUT105
asserted
Output contact
OUT106
asserted
Both
OUT105
and
OUT106
asserted
OUT 7A
7
A
b
Output contact
OUT107
asserted
Output contact
ALARM
asserted
Both
OUT107
and
ALARM
asserted
IN 12
1
2
b
Optoisolated input
IN101
asserted
Optoisolated input
IN102
asserted
Both
IN101
and
IN102
asserted
IN 34
3
4
b
Optoisolated input
IN103
asserted
Optoisolated input
IN104
asserted
Both
IN103
and
IN104
asserted
IN 56
5
6
b
Optoisolated input
IN105
asserted
Optoisolated input
IN106
asserted
Both
IN105
and
IN106
asserted
where:
n
= Event number; defaults to 1 if not listed, where 1 is the
most recent event
S
x
= Displays
x
samples per cycle (4 or 8); defaults to 4 if not
listed
L
y
= Displays
y
cycles of data (1 to LER); defaults to LER if
not listed
L
y
– Displays from cycle
y
to end of report
L
y
–
w
Displays from cycle
y
to cycle
w
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...