4.26
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Control Logic
Relay Word Bits
6
50P21
Winding 2 phase definite-time O/C Level 1 element picked up
50P21T
Winding 2 phase definite-time O/C Level 1 element timed out
50P22
Winding 2 phase instantaneous O/C Level 2 element picked up
51P2
Winding 2 phase inverse-time O/C element picked up
51P2T
Winding 2 phase inverse-time O/C element timed out
51P2R
Winding 2 phase inverse-time O/C 51P2 element is reset
PDEM2
Winding 2 phase demand current threshold exceeded
OCB
O/C element B-phase selection
7
50A23
Winding 2 A-phase instantaneous O/C Level 3 element picked up
50B23
Winding 2 B-phase instantaneous O/C Level 3 element picked up
50C23
Winding 2 C-phase instantaneous O/C Level 3 element picked up
50P23
50A23 + 50B23 + 50C23
50A24
Winding 2 A-phase instantaneous O/C Level 4 element picked up
50B24
Winding 2 B-phase instantaneous O/C Level 4 element picked up
50C24
Winding 2 C-phase instantaneous O/C Level 4 element picked up
50P24
50A24 + 50B24 + 50C24
8
50N21
Winding 2 residual definite-time O/C Level 1 element picked up
50N21T
Winding 2 residual definite-time O/C Level 1 element timed out
50N22
Winding 2 residual instantaneous O/C Level 2 element picked up
51N2
Winding 2 residual inverse-time O/C element picked up
51N2T
Winding 2 residual inverse-time O/C element timed out
51N2R
Winding 2 residual inverse-time O/C 51N2 element is reset
NDEM2
Winding 2 residual demand current threshold exceeded
OC2
Breaker 2
OPEN
command execution
9
50Q21
Winding 2 neg.-seq. definite-time O/C Level 1 element picked up
50Q21T
Winding 2 neg.-seq. definite-time O/C Level 1 element timed out
50Q22
Winding 2 neg.-seq. instantaneous O/C Level 2 element picked up
51Q2
Winding 2 neg.-seq. inverse-time O/C element picked up
51Q2T
Winding 2 neg.-seq. inverse-time O/C element timed out
51Q2R
Winding 2 neg.-seq. inverse-time O/C 51Q2 element is reset
QDEM2
Winding 2 neg.-seq. demand current threshold exceeded
CC2
Breaker 2
CLOSE
command execution
10
50P31
Winding 3 phase definite-time O/C Level 1 element picked up
50P31T
Winding 3 phase definite-time O/C Level 1 element timed out
50P32
Winding 3 phase instantaneous O/C Level 2 element picked up
51P3
Winding 3 phase inverse-time O/C element picked up
51P3T
Winding 3 phase inverse-time O/C element timed out
51P3R
Winding 3 phase inverse-time O/C 51P3 element is reset
PDEM3
Winding 3 phase demand current threshold exceeded
OCC
O/C element C-phase selection
Table 4.10
Relay Word Bit Definitions
(Sheet 2 of 12)
Row
Bit
Definition
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...