G.17
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Distributed Network Protocol
Point Remapping
If the
DNP
command is issued without parameters, the relay displays all of
the maps with the following format:
=>
DNP <Enter>
Binary Inputs = Default Map
Binary Outputs = Default Map
Counters = Default Map
Analog Inputs = 112 28 17 35 1 56 57 58 59 60 61 62 63 64 65 \
66 67 100 101 102 103
Analog Outputs = Off
=>
If the
DNP
command is issued with an object type specified (AI, AO, BI, BO,
C) and the VIEW parameter, the relay displays only the corresponding map.
The S parameter is equivalent to AI VIEW and the T parameter is equivalent
to BI VIEW; they are available for consistency with the older products. If the
map checksum is determined to be invalid, the map will be reported as
corrupted during a display command, as follows:
=>
DNP BI VIEW <Enter>
Binary Inputs = Map Corrupted
=>
If the
DNP
command is issued with just an object type specifier (AI, AO, BI,
BO, C) at level 2 or greater, the relay asks the user to enter indices for the
corresponding list. (The A parameter is the same as AI and B is the same as
BI; these parameters are available for consistency with older products.) The
relay accepts lines of indices until a line without a final continuation character
(\) is entered. Each line of input is constrained to 80 characters, but all the
points may be remapped, using multiple lines with continuation characters (\)
at the end of the intermediate lines. If a single blank line is entered as the first
line, the remapping is disabled for that type (i.e., the relay uses the default
map). If a single entry of OFF or NA is entered, all objects of that type will be
disabled. For example, the first example remap could be produced with the
following commands:
==>
DNP AI <Enter>
Enter the new DNP Analog Input map
112 28 17 \ <Enter>
35 1 56 57 58 59 60 61 62 63 64 65 66 67 100 101 102 \ <Enter>
103 <Enter>
Save Settings (Y/N)?
Y <Enter>
==>
DNP BI <Enter>
Enter the new DNP Binary Input map
<Enter>
Save Settings (Y/N)?
Y <Enter
>
==>
DNP AO <Enter>
Enter the new DNP Analog Output map
OFF <Enter>
Save Settings (Y/N)?
Y <Enter>
==>
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...