7.17
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Serial Port Communications and Commands
SEL ASCII Protocol Details
C
specifies using the eight samples per cycle compressed format for
compatibility with the SEL-2032, SEL-2030, or SEL-2020 and is
equivalent to using the
EVE C
command.
If the Analog Input Label settings (IAW1, etc.) have been renamed, these will
appear in the report as set.
Appendix E: Compressed ASCII Commands
for a complete
description of the command, as well as additional Compressed ASCII
commands
CAS
,
CBR
,
CHI
,
CST
, and
CTA
.
CLO n (Close)
Access Levels B, 2
The
CLO
n
command asserts the CC
n
Relay Word bit. This bit must be
included in the CL
n
Close Logic setting for Breaker
n
, in order for closing to
take place. This logic is described in
.
To close the circuit breaker with this command, type
CLOSE
n
<Enter>
. The
prompting message
Close Breaker n (Y/N) ?
is displayed. Then
Are you
sure (Y/N)?
Typing
N <Enter>
after either of the above prompts aborts the
closing operation with the message
Command Aborted
. If both questions are
answered
Y <Enter>
, the breaker will be closed, an automatic message
summarizing the close operation will be sent, and an Event Report will be
created.
If the main board jumper JMP6B is not in place, the relay responds:
Aborted:
Breaker Jumper Not in Place
.
CON n (Control RBn)
Access Level 2
This command is used to control the Relay Word bit RB
n
, or Remote Bit
n
,
n
having a value of 1 to 16. The relay responds with CONTROL RB
n
. The user
must then respond with one of the following:
SRB
n
<Enter>
(Set Remote
Bit
n
), or
CRB
n
<Enter>
(Clear Remote Bit
n
), or
PRB
n
<Enter>
(Pulse
Remote Bit
n
). The latter asserts RB
n
for one processing interval, one-eighth
cycle. The Remote Bits permit design of SEL
OGIC
control equations that can
be set, cleared, or momentarily activated via a remote command.
COP m n (Copy Settings)
Access Level 2
The
COPY
command copies settings and logic from setting Group
m
to
Group
n
(
m
and
n
can be any combination of 1 through 6). After entering the
settings into one setting group with the
SET
command, copy it to the other
groups with the
COPY
command. Use the
SET
command to modify copied
setting groups. The
ALARM
output contact closes momentarily when you
change settings in an active setting group but not in an inactive setting group.
=>>
COP 1 3 <Enter>
COPY 1 to 3
Are you sure (Y/N) ?
Y <Enter>
Please wait...
Settings copied
=>>
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...