F.3
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Unsolicited SER Protocol
Functions and Function Codes
If the function to enable is not 18 or the function code is not recognized, the
relay responds with an acknowledge message containing a response code 01
(function code unrecognized), and no functions are enabled. If the SER
triggers are disabled, (SER1, SER2, SER3, and SER4 are all set to NA), the
unsolicited SER messages are still enabled, but the only SER records
generated result from settings changes and power being applied to the relay. If
the SER1, SER2, SER3, or SER4 settings subsequently change to any non-NA
value and SER entries trigger, unsolicited SER messages will generate with
the new SER records.
0x02 - Function Code:
Disable Unsolicited
Data Transfer
This function disables the SEL-387 from transferring unsolicited data. The
message format for function code 0x02 is shown below.
The SEL-387 verifies the message by checking the header, length, function
code, and disabled function code against the expected values, and checks the
entire message against the CRC-16 field. If any of the checks fail, except the
function code or the function to disable, the message is ignored.
If an acknowledge is requested as indicated by the least significant bit of the
status byte, the relay transmits an acknowledge message with the same
response number received in the enable message.
If the function to disable is not 18 or the function code is not recognized, the
relay responds with an acknowledge message containing the response code 01
(function code unrecognized) and no functions are disabled.
0x18 - Function:
Unsolicited
Sequence-of-Events
Response
The function 0x18 is used for the transmission of unsolicited Sequential
Events Recorder (SER) data from the SEL-387. This function code is also
passed as data in the “Enable Unsolicited Data Transfer” and the “Disable
Unsolicited Data Transfer” messages to indicate which type of unsolicited
data should be enabled or disabled. The message format for function code
0x18 is shown below.
Data
Description
A546
Message header
10
Message length (16 decimal)
0000000000
Five bytes reserved for future use as a routing address
YY
Status byte (LSB = 1 indicates an acknowledge is requested)
02
Function code
C0
Sequence byte (Always C0.
Other values are reserved for future use in multiple frame messages.)
XX
Response number (XX = 00, 01, 02, 03, 01, 02...)
18
Function to disable (0x18 = Unsolicited SER)
00
Reserved for future use as function code data
cccc
Two byte CRC-16 check code for message
Data
Description
A546
Message header
ZZ
Message length (As many as 34 + 4 · nn decimal, where
nn is the maximum number of SER records allowed per message
as indicated in the “Enable Unsolicited Data Transfer” message.)
0000000000
Five bytes reserved for future use as a routing address
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...