7.25
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Serial Port Communications and Commands
SEL ASCII Protocol Details
SER (Sequential Events Recorder)
Access Levels 1, B, 2
The
SER
command displays the last 512 SER records. To limit the number of
records displayed, use number or date parameters with the
SER
command.
SER d1
shows only events triggered on the date specified by d1.
SER d1 d2
shows only events triggered on or between the specified dates.
SER
m
shows
the most recent m events.
SER
m
n
shows event records
m
through
n
. The
following is an example of the SER report. See
for a complete description of the report.
=>
SER 2/26/97 2/27/97 <Enter>
XFMR 1 Date: 03/13/97 Time: 18:27:42.091
STATION A
FID=SEL-387-X104-V-D970311
# DATE TIME ELEMENT STATE
4 2/26/97 10:33:54.873 TRIP3 Asserted
3 2/26/97 10:33:55.373 TRIP3 Deasserted
2 2/27/97 10:34:06.872 CLS3 Asserted
1 2/27/97 10:34:07.372 CLS3 Deasserted
=>
SER C (Clear Sequential Events Recorder)
Access Levels 1, B, 2
Clear the sequential event records from relay memory with the
SER C
command. The process can take up to 30 seconds under normal operation or
longer if the relay is busy processing a fault or protection logic.
=>>
SER C <Enter>
Clear the SER
Are you sure (Y/N) ?
Y <Enter>
Clearing Complete
=>>
SET (Edit Group 1—6 Settings)
Access Level 2
Configure the relay using the
SET
command. The entire syntax of the
SET
command follows:
S
ET
n
Setting TERSE <Enter>
All parameters are optional and perform the following functions:
➤
n
specifies the setting group (1 through 6). The default is the
active setting group.
➤
Setting
specifies the setting name with which to begin. The
default is the first setting.
➤
TERSE
eliminates the display of the group settings at the end
of the setting procedure. The command will function properly
if just
TE
is entered, instead of the full word.
NOTE:
Clear the SER
Buffer With Care.
Automated clearing of the SER buffer
should be limited to reduce the
possibility of wearing out the
nonvolatile memory. Limit automated
SER C
commands to once per week or
less.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...