7.20
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Serial Port Communications and Commands
SEL ASCII Protocol Details
fault or other protection logic. The following is an example of the
HIS C
command. The relay will pause after the word
Clearing
until the buffer is
completely clear, and then it will display the rest of the information.
=>
HIS C <Enter>
Clear History Buffer
Are you sure (Y/N) ?
Y <Enter>
Clearing Complete
{Relay pauses after the word Clearing}
=>
ID (Identification)
Access Levels 0, 1, B, 2
The
ID
command displays a variety of identification and configuration
information about the relay.
FID: reports the FID string; CID: reports the checksum of the ROM
code; DEVID: reports the terminal ID as set by the TID setting;
DEVCODE: reports the Modbus
®
code (32).
PARTNO: Reports the part number. The last digit of the part number (
p
)
indicates whether the firmware supports DNP communication or not. For
p
= 1, the communications protocol will be standard plus DNP3 Level 2
Slave; for
p
= X, it will be standard with no DNP.
CONFIG: reports nominal frequency, phase rotation, input current, and
PT connections.
The designators “abcdef” represent the following:
“a” the nominal frequency; where 0 = N/A, 1 = 60Hz, and 2 = 50Hz.
“b” the phase rotation; where 0 = N/A, 1 = ABC, and 2 = ACB.
“c” the phase input current scaling; where 0 = N/A, 1 = 5A, and 2 = 1A.
“d” the neutral input current scaling; where 0 = N/A, 1 = 5A, 2 = 1A.
“e” the voltage input connection; where 0 = N/A, 1 = Delta and 2 = Wye.
“f” the current input connection; where 0 = N/A, 1 = Delta and 2 = Wye.
=>>
ID <Enter>
"FID=SEL-387-0-X131-V0-Z002002-D20011105","0903"
"CID=0FA1","0265"
"DEVID=XFMR 1","0838"
"DEVCODE=32","030C"
"PARTNO=0387003X5HXX4XX","064F"
"CONFIG=111100","0387"
=>>
INI (Initialize Interface Boards)
Access Levels 1, B, 2
The
INITIO
command reports the number and type of interface boards in the
relay from Access Levels 1 and B. If the number or type of interface boards
has changed since last power up, INITIO will confirm that the interface boards
present are correct from Access Level 2.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...