5.24
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Metering and Monitoring
Status Monitor
The quantities shown in the
STATUS
report are discussed below. The
applicable limits for warning or failure of each self-test are summarized in
The
{STATUS}
pushbutton on the front-panel interface can also be used to access
the information in the report. See
Section 8: Front-Panel Interface
.
Channel Offset
The relay measures the dc offset (
OS
) voltage of each of the 12 analog current
input channels and compares the value against a fixed limit of 30 mV. If an
offset measurement is outside the fixed limit, the relay declares a warning.
Power Supply
The relay measures the internal power supply (
PS
) voltages and reg5
and -5 voltages, and compares the values against fixed limits. If a voltage
measurement is outside the limits, the relay declares a warning or failure.
Temperature
The relay measures its internal temperatures (
TEMP
). If the relay measures a
temperature less than 40°C or greater than +85°C, it issues a warning. If the
relay measures a temperature less than 50°C or greater than +100°C, it issues
a failure. The temperature warning does not pulse the
ALARM
output contact.
RAM
The relay checks the random-access memory (
RAM
). If a byte cannot be written
to or read from, the relay declares a RAM failure. There is no warning state
for this test.
Flash ROM
The relay checks the flash read-only memory (
ROM
) by computing a checksum.
If the computed value does not agree with the stored value, the relay declares a
ROM failure. There is no warning state for this test.
Analog to Digital
Converter
The relay verifies the A/D converter function by checking the A/D conversion
time. The test fails if conversion time is excessive or a conversion starts but
does not finish. There is no warning state for this test.
Critical RAM
The particular area of RAM where the settings are stored is deemed Critical
RAM. It is verified by computing a checksum. This must agree with a
previously stored checksum value, or the relay will declare a Critical RAM
(
CR_RAM
) failure. There is no warning state for the test.
EEPROM
EEPROM is checked by computing a checksum. If the computed value does
not agree with the stored value, the relay declares a EEPROM failure. There is
no warning state for the test.
Interface Boards
The relay checks the interface board ID register against a stored value. If any
values differ, the relay declares an I/O_BRD failure. There is no warning state
for this test. Use the
INITIO <Enter>
command to reset the stored value for
the new interface board configuration.
Self-Test Alarm Limits
summarizes the limits for issuing warning or failure alarms during
self-testing. The power supply and temperature alarms list the lower values
below which, and upper values above which, the stated alarm is issued.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...