7.35
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Serial Port Communications and Commands
SEL ASCII Protocol Details
The
TARGET
command does not remap the front-panel LEDs. See the
TAR F
command.
The following examples demonstrate the
TARGET
command:
=>>
TAR <Enter>
Default Row is 0
EN TRIP INST 87-1 87-2 87-3 50 51
1 0 0 0 0 1 0 0
=>>
TAR 8 <Enter>
Display and Change Default to Row 8
50N21 50N21T 50N22 51N2 51N2T 51N2R NDEM2 OC2
0 0 0 0 0 1 0 0
=>>
TAR <Enter>
Default Row is 8
50N21 50N21T 50N22 51N2 51N2T 51N2R NDEM2 OC2
0 0 0 0 0 1 0 0
=>>T
AR 8 5 <Enter>
Display Row 8 Five Times
50N21 50N21T 50N22 51N2 51N2T 51N2R NDEM2 OC2
0 0 0 0 0 1 0 0
0 0 0 0 0 1 0 0
0 0 0 0 0 1 0 0
0 0 0 0 0 1 0 0
0 0 0 0 0 1 0 0
=>>
TAR RB4 X <Enter>
Display Row 24 (RB4) But Do Not Change Default
RB1 RB2 RB3 RB4 RB5 RB6 RB7 RB8
0 0 0 0 1 0 0 0
=>>
TAR <Enter>
50N21 50N21T 50N22 51N2 51N2T 51N2R NDEM2 OC2
0 0 0 0 0 1 0 0
=>>
TAR R <Enter>
Reset Default to Row 0
EN TRIP INST 87-1 87-2 87-3 50 51
1 0 0 0 0 0 0 0
=>>
for a list of the Relay Word and the
corresponding rows.
TAR F n (Show Relay Word Targets on Front-Panel LEDs)
Access Levels 1, B, 2
The
TARGET F
command works like the
TARGET
command, but it also
remaps the second row of target LEDs on the front panel to follow the default
row. This may be useful, for example, in testing situations where a display on
the relay front-panel LEDs of element pickup or operation may be desired.
The syntax of the
TAR F
command follows:
TAR F
n k X
<Enter>
➤
n
specifies a new default Relay Word row by entering the
number or the specific Relay Word bit name. If
n
is not
specified, the last default row is displayed.
➤
k
specifies a repeat count for the command for the serial port
display. The default is 1.
➤
X
allows remapping the LEDs to a Relay Word row without
changing the default row.
The default row number returns to 0 when the serial port times out, the
QUIT
command is executed,
TAR 0
command is executed, or the
TAR R
command
is executed.
The front-panel LEDs remain remapped until the front panel times out, the
TAR R
command is executed, or the
{TARGET RESET}
pushbutton is pushed.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...