4.12
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Control Logic
Output Contacts
Operation of Output
Contacts for Different
Output Contact Types
Output Contacts OUT101 through OUT107 and OUT201 through OUT212
The execution of the serial port command
PULSE
xxx
(
xxx
=
OUT101
–
OUT107
,
OUT201
–
OUT212
), asserts the corresponding Relay Word bit (e.g., OUT104) to
logical 1, for one or more seconds as defined by the user. The assertion of
SEL
OGIC
control equation setting OUT
m
(
m
= 101–107, 201–212) to logical 1
also asserts the corresponding Relay Word bit OUT
m
to logical 1.
The assertion of Relay Word bit OUT
m
to logical 1 causes the energization of
the corresponding output contact OUT
m
coil. Depending on the contact type
(a or b), the output contact closes or opens. An a type output contact is open
when the output contact coil is de-energized and closed when the output
contact coil is energized. A b type output contact is closed when the output
contact coil is de-energized and open when the output contact coil is
energized. Solder jumpers JMP22 through JMP29 (main board) and JMP17
through JMP28 (interface board) permit the user to configure any
OUTm
contact to either an a or b type.
OUT101
through
OUT107
are factory-configured
as type a, as are
OUT201
through
OUT212
if the additional interface board is
ordered.
The state of
OUTm
remains the same while a setting change is in progress.
However, once the new settings are enabled, the SEL
OGIC
control equation
setting for
OUTm
will determine the new state of
OUTm
.
OUT107
coil operation may be set to follow that of the
ALARM
contact by setting
jumper JMP23 in the left position on the main board.
OUT107
then will not
respond to Relay Word bit OUT107. The
OUT107
contact configuration can be
set as a or b, as noted above. See
for more information.
ALARM Output Contact
When the relay is functioning properly, the alarm logic/circuitry keeps the
ALARM
output contact coil energized. The type b
ALARM
output contact is
normally held open. Solder jumper JMP21 may also be configured by the user
for a type a contact, if desired.
To verify
ALARM
output contact functionality, execute the serial port command
PULSE NOTALM
. Execution of this command momentarily de-energizes
the
ALARM
output contact coil.
The Relay Word bit NOTALM is asserted to logical 1, and the ALARM output
contact coil is energized, when the SEL-387 is operating correctly. When the
serial port command
PULSE NOTALM
(or front panel
{CNTRL ALARM}
) is
executed, the NOTALM Relay Word bit momentarily deasserts to logical 0.
Also, when the relay enters Access Level 2 or Access Level B or a settings
change is made, the NOTALM Relay Word bit momentarily deasserts to
logical 0. When NOTALM is zero, the ALARM output contact coil is de-
energized momentarily and the b contact falls closed. The
ALARM
contact also
drops closed when a loss of power occurs.
NOTE:
In the SEL-387-5 and
SEL-387-6 Relays with firmware
revisions prior to R600, the NOTALM
Relay Word bit is !ALARM.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...