SET.8 of 36
SEL-387-0, -5, -6 Relay Settings Sheets Example
Group Settings (SET Command)
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Date________________
Winding 2 Demand Metering
Demand Ammeter Time Constant (OFF, 5–255 min)
DATC2
=
15
Phase Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
PDEM2P
=
7.0
(0.1–3.2 A secondary) (1 A)
=
1.4
Neg.-Seq. Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
QDEM2P
=
1.0
(0.1–3.2 A secondary) (1 A)
=
0.2
Residual Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
NDEM2P
=
1.0
(0.1–3.2 A secondary) (1 A)
=
0.2
Winding 3 O/C Elements
Winding 3 Phase O/C Elements
Phase Def.-Time O/C Level 1 PU
(OFF, 0.25–100.00 A secondary) (5 A)
50P31P
=
7.00
(OFF, 0.05–20.00 A secondary) (1 A)
=
1.40
Phase Level 1 O/C Delay (0–16000 cycles)
50P31D
=
0
50P31 Torque Control (SEL
OGIC
control equation)
50P31TC
=
1
Phase Inst. O/C Level 2 PU
(OFF, 0.25–100.00 A secondary) (5 A)
50P32P
=
OFF
(OFF, 0.05–20.00 A secondary) (1 A)
=
OFF
50P32 Torque Control (SEL
OGIC
control equation)
50P32TC
=
1
Phase Inst. O/C Level 3 PU
(OFF, 0.25–100.00 A secondary) (5 A)
50P33P
=
0.50
(OFF, 0.05–20.00 A secondary) (1 A)
=
0.10
Phase Inst. O/C Level 4 PU
(OFF, 0.25–100.00 A secondary) (5 A)
50P34P
=
4.00
(OFF, 0.05–20.00 A secondary) (1 A)
=
0.80
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...