2.14
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Installation
Circuit Board Configuration
Model 0387x0 has only a main board. A Model 0387x1 or
0387xY relay has an extra interface board below the main
board.
Step 5. Disconnect circuit board cables as necessary so you can remove
the board and draw-out tray you want.
a. To remove the extra interface board, first remove the
main board.
b. Remove ribbon cables by pushing the extraction ears
away from the connector.
c. Remove the six-conductor power cable by grasping the
wires near the connector and pulling away from the
circuit board.
Step 6. Grasp the draw-out assembly of the board and pull the
assembly from the relay chassis.
Step 7. Locate the jumper(s) or battery to be changed. Make the
desired changes.
Note that the output contact jumpers are soldered in place.
Step 8. When finished, slide the draw-out assembly into the relay
chassis.
a. Reconnect the cables you removed in
b. Replace the relay front-panel cover.
Step 9. Replace any cables previously connected to serial ports.
Step 10. Re-energize the relay by reconnecting wiring to rear-panel
terminals
+
(
Z25
) and
–
(
Z26
).
On Connectorized versions, replace the power connector at
rear-panel terminals
+
(
Z25
) and
–
(
Z26
).
Main Board
Output Contact Jumpers
to see the layout of the main board and locate the solder
jumpers to the rear of the output contacts. Select the contact type for the
output contacts. With a jumper in the A position, the corresponding output
contact is an a output contact. An a output contact is open when the output
contact coil is de-energized and closed when the output contact coil is
energized. With a jumper in the B position, the corresponding output contact
is a b output contact. A b output contact is closed when the output contact coil
is de-energized and open when the output contact coil is energized. These
jumpers are soldered in place but may be changed in the field.
Note that the
ALARM
output contact is a b contact and that the other output
contacts are all a contacts. This is the normal configuration of these jumpers in
a standard relay shipment. The additional interface boards have slightly
different layout locations for the jumpers relative to the corresponding output
contacts.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...