7.34
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Serial Port Communications and Commands
SEL ASCII Protocol Details
STA (Status Report)
Access Levels 1, B, 2
The
STATUS
command displays a report of the self-test diagnostics. The
relay automatically executes the
STATUS
command whenever the self-test
software enters a warning or failure state. You can repeat the
STA
command
by appending a number as a repeat count parameter. Type
STA 4 <Enter>
to
view the status information four times.
If a warning or failure state occurs, the next time the
STA
command is issued,
the warning state is reported. If a warning or failure occurs, it will not be
cleared until relay power is cycled and the problem is fixed. Saving relay
settings performs a warm boot of relay logic. This can clear some warnings,
but do not ignore warnings; contact the factory.
The
STA C <Enter>
command clears any out-of-tolerance condition from the
status report and reboots the relay. Do not ignore warnings; contact the
factory.
If the Analog Input Label settings (IAW1, etc.) have been renamed, these will
appear in the report as set. The STATUS report format appears below:
XFMR 1 Date: 04/21/00 Time: 21:29:42.829
STATION A
FID=SEL-387-6-X117-V0-Z001001-D20000419 CID=2001
SELF TESTS
W=Warn F=Fail
IAW1 IBW1 ICW1 IAW2 IBW2 ICW2
OS 0 -0 -0 1 0 1
IAW3 IBW3 ICW3 IAW4 IBW4 ICW4
OS 0 0 -0 1 0 -1
+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS
PS 4.93 4.99 -5.07 11.90 -12.08 14.96 -14.90
TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD
32.1 OK OK OK OK OK OK
Relay Enabled
_
=>
TAR (Show Relay Word Targets On-Screen)
Access Levels 1, B, 2
The
TARGET
command displays the default row of the Relay Word showing
the Relay Word bit names and their value, which is either a logical 1 (asserted)
or logical 0 (deasserted). The syntax of the
TAR
command follows:
TAR
n k X
<Enter>
➤
n
specifies a new default Relay Word row by entering the row
number or the specific Relay Word bit name (except names of
target elements in rows 0 and 1). If
n
is not specified, the last
default row is displayed.
➤
k
specifies a repeat count for the command. The default is 1.
➤
X
allows viewing a Relay Word row without changing the
default row.
The default row number can also be changed by the
TAR F
command, but
each serial port has independent defaults. The default row number returns to 0
when the port times out, the
QUIT
command is executed,
TAR 0
command is
executed, or the
TAR R
command is executed.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...