background image

INSTRUCTIONS 

GEH-2024A 

SUPERSEDES 

GEH·2024 

MULTICONTACT  AUXILIARY 

RELAY 

Type  HFA51 

DESCRIPTION 

INTRODUCTION 

The  HFA51A  and  HFA51B  relays  are  instant­

aneous,  hinged  armature,  multi-contact,  auxiliary 

relays.  They  have  six  electrically  separate  contact 

circuits  adaptable  for  either  circuit  opening  or 

circuit  closing  application.  This  arrangement  per­

mits  a  number  of  operations  to  be  performed 

simultaneously. 

The  HFA51A  and  HFA51B  relays  are  available 

for  front  or  back  connection. 

The  front  con­

nected  relays  are  suitable  for  surface  mounting 

only. 

peres  continuous 

or 

30 

amperes  for  one  minute. 

Table  II  lists  the  non-inductive  interrupting capacity 

of  each  contact. 

TABLE  I 

Code  No. 

60 

51 

42 

33 

24 

15 

06 

Position  No. 

Contact 

The  back  connected  relays  are  suitable  for 

either  surface  mounting  or  semi-flush  mounting;  a 

Note:  a 

Normally  Open 

Normally  Closed 

steel  flange  is  necesssary  for  the  latter.  There  are 

two  types  of  flanges  available:  one  provides  mount-

TABLE 

II 

ing  with  normal  cover;  one  provides  mounting  with 

the  drawout-case  type  cover. 

CHARACTERISTICS 

The  HFA51A  relay  is  self  reset  and  has  an 

instantaneops  dropout. 

The  HFA51B  relay  is  hand  reset  by  means  of  a 

plunger  assembly  installed  through  the  transparent 

cover. 

Unless  the  relays  are  ordered  with  a  specific 

contact  arrangement,  they  will  be  shipp�d  with  six 

circuit  closing  contacts  (Code 

60). 

The  contact 

arrangement  can  be  easily  changed  to  provide  any 

of  the  combinations  shown  in  Table  I. 

RATINGS 

DC 

AC 

Volts 

Volts 

12 

30 

115 

30 

24 

15 

230 

20 

32 

1

460 

15 

4

575 

1

1

2

250 

8URDENS 

The  burdens  are  measured  with  the  relay  in 

the  picked  up  position  and  at  rated voltage  are  listed 

in  Table 

III. 

TABLE 

The  Type  HFA  relays  are  available  with  coil 

DC  COILS 

AC  COILS 

,5 

atings  for  standard  voltages  up  to  575  volts  at  25, 

Watts 

Freq. 

Volt-

0, 

or 

60 

cycles  and  up  to  250  volts  d-e. 

Cold 

Hot 

Cycles 

Amperes 

Watts 

7.8 

6.0 

25 

10 

The  current  closing  rating  of  each  contact  is 

30 

5

23 

mperes.  The  current  carrying  rating  is  12  am-

60 

32 

12 

Theae  inatruction1  do  not  purport  to  cover  all  detail•  or  variation•  in  equipment  nor  to  provide  for  every  pouible 

contingency  to  be  met  in  connection  with  inllallation,  operation  or  maintenance.  Should  further  information  be  deaired 
or  ahould  particular  problema  ari�&  which  are  not  covered wfficiently  for  the  purchaaer'•  p41rpoae•,  the  maHer  mould 
be  referred  to  the  Generol  Electric  Company. 

LOW  VOLTAGE  SWITCHGEAR  DEPARTMENT 

GENERAL

ELECTRIC 

PHILADELPHIA,  PA. 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Содержание HFA51A

Страница 1: ...elay is hand reset by means of a plunger assembly installed through the transparent cover Unless the relays are ordered with a specific contact arrangement they will be shipp d with six circuit closing contacts Code 60 The contact arrangement can be easily changed to provide any of the combinations shown in Table I RATINGS DC AC Volts Amperes Volts Amperes 12 30 115 30 24 15 230 20 32 10 460 15 48...

Страница 2: ... relays is shown in Fig 5 ADJUSTMENTS PICKUP The relays are adjusted at the factory to pickup at 80 percent of rating for a c coils and 60 percent 2 of rating for d e coils Normally these adjust ments should not change if it is necesssary to readjust the relay the knurled adjusting nut should be lifted 1 16 inch turned clockwise to raise pick up or counterclockwise to lower pickup and then reseate...

Страница 3: ...sists of a flexible strip of metal with an etched roughened surface resembling in effect a superfine file The polishing action is so delicate that no scratches are left yet corroded material will be removed rapidly and thoroughly Fine silver contacts should not be cleaned with knives files or abrasive paper or cloth rr 1 9 8 I 6 8 1 t 5 J OUHIIIE 9 16 d 6 i6 6_ _ 16 The burnishing tool described i...

Страница 4: ... Mounted Type HFA Relays Typical Model lumber is HFA51 F STUD 5 31 NO S 21 32 OUTLINE 1 1 3 2 r a Ir r EL I fl f l I6 DIA 2 tiOLES I f PANEL DRILLING FRONT VIEW Fig 9 Outline and Panel Drilling for Front Connected Type HFA Relay Typical Model lumber is HFA51A H Denotes change from superseded book GENERAL ELECTRIC COMPANY PHILADELPHIA PA 0 I CIO co ICII co co ao J fit ao 0 en g u w w w E l e c t r ...

Отзывы: