Sauter flexotron®800
ventilation
Installation and wiring
P100012082
28
3.10
Empty wiring diagram RDT815
-
LS
Power supply 24 V AC or 24 V DC,
±15%. 50/60 Hz
1
D+
RS485 Modbus (not with
web (TCP/IP) models)
-
MM
2
D-
-
Earth conductor
3
C
-
+24 V +24 V DC. Reference point for digital inputs DI
4
E
42
LS
Reference point for digital outputs DO
-
-
-
41
DO1
-
-
40
DO2
-
-
39
DO3
38
DO4
9
DI1
10
DI2
34
Reference potential for analogue inputs AI
11
DI3
33
AI1
12
DI4
32
AI2
31
Reference potential for analogue inputs AI
17
Reference potential for analogue
outputs AO
30
AI3
18
AO1
29
AI4
19
AO2
20
AO3
3.11
Empty wiring diagram RDT808
-
LS
Supply voltage 24 V AC or 24 V DC,
±15%. 50/60 Hz
1
D+
RS485 Modbus (not in
WEB (TCP/IP) models)
-
MM
2
D-
-
Protective earth
3
C
-
+24 V
+24 V DC. Reference for digital inputs DI.
4
E
42
LS
Reference for digital outputs DO.
-
-
-
41
DO1
-
-
40
DO2
-
-
34
Reference pole for analogue inputs AI
9
DI1
33
AI1
10
DI2
32
AI2
11
DI3
17
Reference pole for analogue outputs
AO
18
AO1