18.7
Start-up wizard
The start-up wizard is a function that can be activated in "Configuration"/"System". See
the section Activation of start-up wizard.
If the wizard has been activated, the operator will access a number of menus at power-
up. These menus contain certain operation parameters that should be set.
The wizard is useful when the controller is delivered pre-configured together with an air
handling unit. After the controller has been configured, the manufacturer of the air
handling unit will activate the start-up wizard, which will help the operator to set setpoint
values, running times etc. without having to log on.
In the first menu, the language is chosen.
Choose language
English
In the second menu, the setpoint is set. The appearance of the menu depends on
which control type has been configured.
Supply air temp
Setp.: 18°C
In the third menu, time and date are set.
Time: 14:27
Date: 2008-11-25
Weekday: Tuesday
In the fourth menu, the running time for normal speed Monday --- Friday is set.
Normal speed
Monday
Friday
Per 1: 07:00 – 16:00
Per2: 00:00 – 00:00
In the fifth menu, the running time for normal speed Saturday, Sunday and holiday is
set.
Normal speed
Saturday
Holiday
Per 1: 00:00 – 00:00
Per2: 00:00 – 00:00
If 2-speed fans or pressure/flow controlled fans have been configured, the
corresponding times for reduced speed will be displayed in the sixth and seventh
menus.
Reduced speed
Monday
Friday
Per 1: 07:00 – 16:00
Per2: 00:00 – 00:00
Reduced speed
Saturday
Holiday
Per 1: 00:00 – 00:00