Sauter flexotron®800
ventilation
Functional description
P100012082
42
5.1.7
Cooling recovery
If the extract air temperature is a settable amount lower than the outdoor temperature,
cooling recovery can be activated. When cooling recovery is activated the heat
exchanger signal will be reversed to give increasing recovery on increasing cooling
demand. The function also activates the heating function
‘‘Free heating’’: if heating is
required and the outdoor temperature is higher than the extract air temperature,
outdoor air will primarily be used.
Output signals
Controller signal
0%
100%
Exchanger
Cooling
In- and outputs
AI
Outdoor temperature sensor
AI
Extract air sensor
5.1.8
Enthalpy control
Calculating the enthalpy means to calculate the energy content of the air, taking into
consideration both the temperature and the air humidity. The value is given in energy
per kilogram air (kJ/kg). If enthalpy control is configured, the enthalpy is calculated both
indoors and outdoors. If the enthalpy is higher outdoors than indoors, the recirculation
damper will be overridden to increase the recirculation. The function is not active when
using free cooling, in this case outdoor air is used for cooling the room instead. For the
enthalpy calculation to be made, four sensors are required:
In- and outputs
AI
Outdoor temperature sensor
AI
Outdoor humidity sensor
AI
Room/Extract air temperature sensor
AI
Room humidity sensor
5.1.9
Heat exchanger efficiency monitoring
General
The function calculates the heat exchanger temperature efficiency in percent when the
output signal to the exchanger is higher than 5 % and the outdoor temperature is lower
than 10°C.
When the control signal is lower than 5 % or the outdoor temperature is higher than
10°C the display will show 0 %.
The heat exchanger efficiency is calculated using the following formula:
Efficiency = (Extractairtemp – Exhaustairtemp) /
(Extractairtemp – Outdoortemp) * 100