Sauter flexotron®800
ventilation
Settings
P100012082
74
Shutdown mode
Shutdown mode
P-band: 100.0 °C
I-time: 100 sec
Frost protection temperature
Frost protection
temperature
Frost protection
Active
Setp shutdown: 25°C
P-band active: 5°C
Fast stop at
frost-protection alarm
Yes
"Setp shutdown" is the shutdown mode setpoint.
P-band active 5°C means that the frost protection controller will start overriding the
heating output when the frost protection temperature is less than five degrees above
the set frost alarm limit. The default alarm limit is 7°C. It can be changed in the menu
Settings/Alarm settings/Alarm limits/Alarm limit frost protection.
Exchanger de-icing
De-iceing
P-band: 100 °C
I-time: 100 sec