Sauter flexotron®800
ventilation
Temperature
P100012082
63
Setpoint. Control mode 3 and 5: Cascaded room temperature control.
Room temp.1
Actual: 22.0°C
Setpoint: 21.5°C
In control mode five, the setpoint is used when cascade connected room control is
active.
Submenu for setting the min and max limitation temperatures for the supply air.
If cascade control
max/min supply setp.
Max: 30.0°C
Min: 12.0°C
If two room sensors have been configured you will also get the following menu:
Room temp.2
Actual: 21.8°C
Setpoint. Control mode 4 and 6: Cascade connected extract air temperature
control.
Extract air temp.
Actual: 21.0°C
Setpoint: 21.1°C
In control mode six, the setpoint is used when cascade connected extract air control is
active.
Submenu for setting the min and max limitation temperatures for the supply air.
If cascade control
max/min supply setp.
Max: 30.0°C
Min: 12.0°C
Support control heating
Support heating
Room temp for
Start: 15.0°C
Stop: 21.0°C
Support control cooling
Support cooling
Room temp for
Start: 30.0°C
Stop: 28.0°C
Frost protection temperature
Frost protection
Actual: 30.9°C
De-icing exchanger
De-icing exchanger
Actual: 11.2°C
Setpoint: -3.0°C
Hysteresis: 1.0°C