Sauter flexotron®800
ventilation
Configuration
P100012082
88
16.11 Support control
If you select the function support control without EAF (extract air fan), a recirculation
damper must be used. See more in section 5.1.5.
Support control
Active: Yes
EAF running during
support contr: Yes
Minimum running time
Min. run time for
support ctrl: 20 min
For detailed description, see 5.1.5 Support control.
16.12 CO2/VOC Demand control
CO2/VOC active
Never
Type: Mixing dampers
Min. time: 20 min
Activation level
1/2-speed: 800 ppm
1/1-speed: 1000 ppm
diff: 160 ppm
There is a detailed description in section 5.4.2, 'Demand-led ventilation'.
16.13 Fire function
Fire dampers are normally configured to open on fire alarm. However, via the display
you can configure them to be normally open instead.
You can use CASE flexotron® to configure
the air handling unit’s running mode on fire
alarm. The following choices are possible: "stopped", "continuous run", "run via normal
start/stop conditions", "only supply air fan in operation", "only extract air fan in
operation".
There is a digital input for detection of open and closed position of the fire dampers.
All dampers must be wired to the same output in order to get correct results.
Fire damper function
Not active
Operation when alarm
Stopped
Select if fire alarm should be normally closed or normally open and activation of fire
damper exercising if the unit should be stopped or not:
’’No’’, ’’Yes unit running’’
,
’’Yes
unit stopped
’’
,
Fire alarm input
Normally open
Damper exercise
No