Alarm text
Pri
Description
21 High extract air temp
B
High extract air temp during extract air control
22 Low extract air temp
B
Low extract air temp during extract air control
23 Electric heating is
overheated
A
Heater high temperature limit switch activated
24 Frost risk
B
Frost protection function is overriding the control
of the heater output
25 Low frostguard temp
A
Frost protection temperature below frost limit
value
26 Low efficiency
B
Heat exchanger efficiency below limit value
27 Sensor error Outdoor
temp
B
Malfunction of connected sensor
28 Analogue de-icing
-
Exchanger de-icing activated by de-icing sensor
29 Rotation guard
exchanger
B
Exchanger rotation sentinel alarm activated
30 Fire damper is out of
operation
B
Fire damper exercise test failed
31 Supply Air Fan control
error
-
Supply air pressure deviates too much from the
setpoint for too long.
32 Extract Air Fan control
error
-
Extract air pressure deviates too much from the
setpoint for too long.
33 Supply Air Fan
external operation
C
SAF run-signal received when unit is stopped
34 Extract Air Fan
external operation
C
EAF run-signal received when unit is stopped
35 Ventilation Manual
mode
C
The unit is in manual mode
36 Manual supply air
control
C
Supply air temp controller in manual control
37 Manual supply Air Fan
mode
C
Supply air fan in manual control
38 Manual Supply Air
C
The SAF is in manual mode
39 Manual Extract Air
Fan mode
C
Extract air fan in manual control
40 Manual Extract Air
C
The EAF is in manual mode
41 Manual Heater Control C
The heater is in manual mode
42 Manual exchanger
control
C
Heat exchanger output in manual control
43 Manual cooler control C
Cooling output in manual control
44 Manual P1-Heater
C
Heating circulation pump in manual control
45 Manual P1-Exchanger C
Exchanger circulation pump in manual control
46 Manual P1-Cooler
C
Cooling circulation pump in manual control
47 Fire damp. Manual
C
Fire dampers in manual control
48 Internal battery error
A
Internal battery needs replacing
49 Sensor error Supply
Air temp
B
Malfunction of connected sensor