Configuration
P100012082
105
16.28.7 Outdoor temp. for control mode change
If the unit is configured for combined Supply air/Room control this menu permits the
setting of the change-over outdoor temperature.
Outdoor temp for
control mode change
13.0°C
16.28.8 Split of optional temp. sequence
Any one of the analogue temperature control output sequences "Y1", "Y2" and "Y3" can
be split, for example to control two heating valves in sequence. The split is always
even, 50/50, which means that each part of the split will have half the part of the P-band
assigned to the output. An analogue output must be assigned to the output signal
‘‘Split’’. On increasing output demand, the regular output is always run first and then the
output that has been configured as Split.
Split optional
temperature sequence
Y1 Y2 Y3
No split
16.28.9 Fast stop on overheating
If this function is active, the fans will be immediately stopped when there is an
overheating alarm, regardless of the set cool-down time.
Fast stop on alarm
“Electric heating is
overheated”: No
54%
50%
32%
30%
0%
0%
Controller
signal
Cooling
Heating
Heat
exch.
Output signal
100%
100%
Heat demand